Common Calculation Mistakes on the Journeyman Exam
Most wrong answers on calculation questions are not math errors. They are setup errors: the right formula with the wrong input, or the right table with the wrong column. The good news is that these mistakes repeat, so you can learn to catch them. Here are ten of them, each with a short example showing the wrong answer and the right one.
1. Doubling the length twice in voltage drop
The single-phase formula VD = 2 × K × I × L / CM already includes the 2 for the return conductor. L is the one-way length.
If the question says "total conductor length" or "round trip", divide by 2 before you use the formula. Full walkthrough: how to calculate voltage drop.
2. Using 2 instead of 1.732 for three-phase
The wrong answer is about 15.5% too high (2 / 1.732 = 1.155). The same mix-up happens in power and current formulas: three-phase current is P / (1.732 × E), single-phase is P / E.
3. Sizing motor conductors from the nameplate
Article 430 wants the table full-load current (Tables 430.248 and 430.250) for conductors and the short-circuit device, and the nameplate current for overloads.
Here both happen to lead to the same wire size, but on a test with tight answer choices the difference can be one size. More in motor circuit calculations.
4. Forgetting 125% for continuous loads
A continuous load runs for three hours or more. Branch circuits for continuous loads are sized at 125% of the continuous part (210.19(A) and 210.20(A)), and feeders follow the same idea in 215.2 and 215.3.
5. Leaving the ground out of conduit fill
Equipment grounding conductors count in conduit fill.
See conduit fill step by step for the full method.
6. Box fill: grounds, yokes and clamps
Three counting errors show up again and again: counting every ground wire separately (all together count as 1), counting a device yoke as 1 (it counts as 2), and forgetting internal clamps (1, based on the largest conductor).
More in box fill calculation examples.
7. Ignoring the terminal temperature rating
THHN has a 90 °C rating, but most terminations are rated 60 °C or 75 °C. Under 110.14(C), the conductor cannot be used above the ampacity of the column that matches the terminals.
Use the 90 °C column only as the starting point for derating, then compare with the terminal column. See ampacity and derating.
8. Mixing up the derating order or the column
Temperature correction and bundling adjustment both multiply the same base value, and both must use the factors for the same insulation column.
The order of the two multiplications does not change the result, but mixing columns does.
9. Applying the lighting demand factor to the whole load
In the dwelling standard calculation, the first 3,000 VA stays at 100%. Only the portion above it gets the 35% factor.
That error alone takes almost 2,000 VA out of the service calculation. Walkthrough: residential load calculation.
10. Rounding too early
Rounding in the middle of a problem can push a borderline answer across a line.
Keep full values on your calculator until the last step, then round once, in the direction the code requires: up for minimum sizes, down for maximum protection like the multi-motor feeder rule in 430.62.
A two-minute check before you pick an answer
- Single-phase or three-phase? Is 1.732 in the formula only where it belongs?
- Right current? Table FLC or nameplate, continuous or not.
- Right length? One-way for voltage drop.
- Right column? Insulation for derating, terminals for the final limit.
- Everything counted? Grounds in conduit fill, yokes and clamps in box fill.
- Rounded once, in the right direction?
The fastest way to fix these mistakes is to work problems where you can see every step. The voltage drop calculator shows each line of the calculation, and you can get 5 worked problems in your inbox.
Frequently asked questions
What is the most common voltage drop mistake?
Using round-trip length in the single-phase formula, which already includes a 2 for the return conductor. That doubles the answer.
Should I round during a calculation?
Keep full values until the last step, then round once in the direction the code requires: up for minimum sizes, down for maximum protection limits.
Which column of Table 310.16 should I use?
Start derating from the insulation temperature column, often 90 degrees C for THHN, then compare the result with the column that matches the terminal rating, usually 60 or 75 degrees C.
Why does my box fill answer come out too small?
Usually because the device yoke was counted as one instead of two, internal clamps were left out, or grounding conductors were counted separately instead of as one.